Extended-Interval Inspection and Testing Requirements

Tuesday, February 21, 2017
Fire Protection System

Did you know that NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems (2011 edition) includes inspection and testing requirements beyond the more common monthly, quarterly and annual procedures?

These extended-interval inspection and testing requirements include, but are not limited to the following:

  • Dry-Pipe and Preaction Systems – pressure test for air leakage every 3 years.
  • Dry-pipe Systems – full flow trip test every 3 years.
  • Internal inspection of check valves – every 5 years.
  • Internal inspection of piping – every 5 years.
  • Gauges – recalibrate or replace every 5 years
  • Sprinklers – sample testing or replacement. The required frequency for this varies from every 5 years to every 75 years depending on the type of sprinkler and the environment in which the sprinkler is installed.

Please refer to NFPA 25 for more details.