Extended-Interval Inspection and Testing Requirements

Fire Protection System

Did you know that NFPA 25 Standard (2011 edition) has extra fire system inspection, testing, and maintenance requirements for Water-Based Fire Protection Systems? These requirements are in addition to the regular monthly, quarterly and annual procedures.

NFPA 25 Testing Requirements For Extended-interval Inspection and Testing

These extended-interval fire system inspection and testing requirements include, but are not limited to the following:

  • Dry-Pipe and Preaction Systems – pressure test for air leakage every 3 years.
  • Dry-pipe Systems – full flow trip test every 3 years.
  • Internal inspection of check valves – every 5 years.
  • Internal inspection of piping – every 5 years.
  • Gauges – recalibrate or replace every 5 years
  • Sprinklers – sample testing or replacement. The required frequency for fire sprinkler system testing or replacement varies from every 5 years to every 75 years depending on the type of sprinkler and the environment in which the sprinkler is installed.

Please refer to NFPA 25 testing requirements for more details.

Ahern is Your One-stop Source For Fire System Inspection, Testing, & More.

From design to installation, maintenance, inspection, and repair of fire protection systems, Ahern has the team of NICET certified designers, in-house fabrication resources, and experienced field teams to meet your needs. Our service team is trained to identify and inform you of potential hazards and code compliance issues that may adversely impact your systems. We  utilize an electronic inspection and testing system which can alert building owners when extended-interval items are approaching their due date. 